Wiring a circuit? THHN and NM-B wire on Amazon (opens in a new tab)

Wire Size Calculator

Find the right wire gauge for any circuit from the amps, the voltage and the length of the run, checked for both ampacity and voltage drop.

Length in
A

The breaker size for a circuit, or the nameplate amps of the equipment.

V
ft

From the panel to the load, measured along the cable route.

Use 60°C unless the wire and both terminals are rated 75°C. Circuits of 100 A or less default to 60°C.

Minimum wire size —
Wire sizes compared for this circuit

All wire and conductor calculators

How to use the wire size calculator

  1. Enter the load current. For a new circuit, use the breaker size. For one appliance, use the amps on its nameplate.
  2. Enter the voltage (120, 240, 208, 480, or 12 or 24 for DC) and the one-way length of the run, from the panel to the load.
  3. Pick copper or aluminum, and single-phase or three-phase.
  4. Pick the temperature rating. NM-B (Romex) cable is always sized at 60°C. Individual THHN/THWN wires in conduit can use 75°C when the breaker and the equipment terminals are rated 75°C, which most modern ones are.
  5. Tick continuous load for anything that runs for three hours or more, such as an EV charger, a water heater or electric heat.

The calculator finds the smallest wire that carries the current and keeps the voltage drop under your limit, and shows the sizes either side so you can compare.

Two checks: ampacity and voltage drop

A wire has to pass two separate tests:

On short runs ampacity decides the size. On long runs, voltage drop usually takes over and calls for a bigger wire.

The formula

The voltage drop of a single-phase or DC circuit is:

Vd = 2 × I × R × L ÷ 1,000

For three-phase circuits, replace the 2 with 1.732 (the square root of 3).

Example: a 40 A, 240 V circuit 100 ft long in copper NM-B cable. At 60°C, 8 AWG copper is rated 40 A, so it passes the ampacity test. Its resistance is 0.778 Ω per 1,000 ft, so Vd = 2 × 40 × 0.778 × 100 ÷ 1,000 = 6.2 V, which is 2.6% of 240 V. That is under 3%, so the answer is 8 AWG copper.

Wire size chart by amps

For short runs where voltage drop is not a problem. Longer runs may need a bigger wire.

CircuitCopper, 60°C (NM-B)Copper, 75°C (THHN)Aluminum, 75°C
15 A14 AWG14 AWG12 AWG
20 A12 AWG12 AWG10 AWG
30 A10 AWG10 AWG8 AWG
40 A8 AWG8 AWG8 AWG
50 A6 AWG8 AWG6 AWG
60 A4 AWG6 AWG4 AWG
80 A3 AWG4 AWG2 AWG
100 A1 AWG3 AWG1 AWG

Small wires have their own limits in NEC 240.4(D): 14 AWG copper on no more than a 15 A breaker, 12 AWG on 20 A and 10 AWG on 30 A, whatever the table says. More detail is in what size wire for 15 to 100 amps.

Things the calculator does not cover

Frequently asked questions

What size wire do I need for 50 amps?

6 AWG copper in NM-B cable, or 8 AWG copper THHN in conduit where everything is rated 75°C. In aluminum, 6 AWG. Runs longer than about 100 ft at 240 V may need one size larger for voltage drop.

Can I use a bigger wire than the calculator says?

Yes. A larger wire is always allowed and lowers the voltage drop; it only costs more and can be harder to fit in the breaker and device terminals. Never use a smaller one.

Does the neutral need to be the same size?

Usually yes for branch circuits. The equipment ground can be smaller: NEC Table 250.122 sets its size from the breaker rating.

Latest guides

All guides