Wire Ampacity Chart

How many amps a copper or aluminum wire can carry, from NEC Table 310.16, corrected for hot locations and for several circuits run together.

The hottest air the wire runs through, such as an attic in summer.

In one conduit or cable. Count hots, and neutrals that carry unbalanced current. Grounds do not count.

Corrected ampacity —
Ampacity chart (NEC Table 310.16)

How to use the ampacity calculator

  1. Pick copper or aluminum, the wire size and the insulation temperature rating (printed on the wire jacket, see below).
  2. Pick the ambient temperature: the hottest air around the wire along its route. A summer attic can reach 120 to 150°F.
  3. Enter the number of current-carrying conductors in the same conduit or cable.

The calculator takes the value from the wire ampacity chart and applies both corrections. The chart below the result shows every size, with your corrected column on the right.

The formula

Corrected ampacity = table ampacity × temperature factor × adjustment factor

The table values assume no more than three current-carrying conductors in an ambient of 30°C (86°F). Hotter air and crowded conduits both reduce what the wire can carry, because the heat has nowhere to go.

Example: 12 AWG copper THHN (90°C, 30 A in the table) runs through an attic at 41 to 45°C, with six current-carrying conductors in one conduit. 30 × 0.87 × 0.80 = 20.9 A. That still supports a 20 A breaker.

Ampacity chart (NEC Table 310.16)

SizeCopper 60°CCopper 75°CCopper 90°CAluminum 75°C
14 AWG152025—
12 AWG20253020
10 AWG30354030
8 AWG40505540
6 AWG55657550
4 AWG70859565
2 AWG9511513090
1/0 AWG125150170120
2/0 AWG145175195135
4/0 AWG195230260180
250 kcmil215255290205
500 kcmil320380430310

Values in amps, for not more than three current-carrying conductors at 30°C (86°F) ambient. 14, 12 and 10 AWG are also limited by NEC 240.4(D) to 15, 20 and 30 A breakers in copper.

Which temperature column?

  • 60°C: NM-B (Romex) and UF cable must use this column, even though the wires inside are rated 90°C. Also used for terminals on circuits of 100 A or less unless they are marked 75°C.
  • 75°C: THWN, XHHW, SE and USE wire, and the usual limit for breakers, panels and lugs.
  • 90°C: THHN, THWN-2 and XHHW-2. You can start derating from the 90°C value, but the final result may not exceed the ampacity of the column the terminals are rated for (NEC 110.14(C)).

More on these letters in THHN vs THWN-2 and other wire types.

Correction and adjustment factors

Current-carrying conductorsAdjustment
1 to 3100%
4 to 680%
7 to 970%
10 to 2050%
21 to 3045%
31 to 4040%
41 and more35%

Equipment grounding wires never count. A neutral counts when it carries the unbalanced current of a multiwire circuit or of non-linear loads such as LED drivers. Conduit nipples 24 in or shorter need no bundling adjustment.

Frequently asked questions

How many amps can 12 gauge wire carry?

12 AWG copper is rated 20 A at 60°C, 25 A at 75°C and 30 A at 90°C, but it may only be protected by a 20 A breaker. The higher values are useful when you have to derate it.

Why is aluminum rated lower?

Aluminum has about 61% of copper’s conductivity, so the same size heats up more. It takes roughly two sizes larger to carry the same current.