AWG Wire Gauge Chart
Diameter, area in mm² and circular mils, and copper resistance for every AWG size from 4/0 to 40, with a converter from diameter or mm² to the nearest gauge.
How to use the AWG chart
Pick a gauge to see its diameter, area and resistance. To identify an unknown wire, choose find the gauge from a diameter, strip a little insulation and measure the bare metal with a caliper. To convert a metric (IEC) size, choose find the gauge from an area in mm². The full AWG wire gauge chart below the result highlights the gauge you picked.
How the AWG system works
American Wire Gauge numbers come from the number of drawing steps in old wire mills, which is why a bigger number means a thinner wire. The sizes follow a fixed formula:
d = 0.005 in × 92(36 − n) ÷ 39
Here n is the gauge number; 1/0 is n = 0, 2/0 is n = −1, 3/0 is −2 and 4/0 is −3. Three useful rules follow from it:
- Every 3 gauges the area, and the weight, roughly doubles or halves, and the resistance does the opposite.
- Every 6 gauges the diameter doubles or halves.
- Every 10 gauges the area changes about ten times. 10 AWG copper is close to 1 Ω per 1,000 ft.
Read more in AWG explained.
Common building-wire sizes
| AWG | Diameter (in) | Diameter (mm) | Area (mm²) | Nearest metric size |
|---|---|---|---|---|
| 14 | 0.0641 | 1.628 | 2.08 | 2.5 mm² |
| 12 | 0.0808 | 2.053 | 3.31 | 4 mm² |
| 10 | 0.1019 | 2.588 | 5.26 | 6 mm² |
| 8 | 0.1285 | 3.264 | 8.37 | 10 mm² |
| 6 | 0.1620 | 4.115 | 13.3 | 16 mm² |
| 4 | 0.2043 | 5.189 | 21.2 | 25 mm² |
| 2 | 0.2576 | 6.544 | 33.6 | 35 mm² |
| 1/0 | 0.3249 | 8.252 | 53.5 | 70 mm² |
| 4/0 | 0.4600 | 11.68 | 107 | 120 mm² |
Solid-wire diameters. Stranded wire of the same gauge has the same metal area but measures a few percent larger across. The “nearest metric size” is the next IEC size up, the safe direction when you swap a metric cable for an AWG one.
kcmil sizes
Above 4/0, wire is sized in thousands of circular mils (kcmil, once written MCM). A circular mil is the area of a circle one thousandth of an inch across, so a wire’s area in circular mils is simply its diameter in mils squared. 4/0 is 211.6 kcmil, so the next size up is 250 kcmil.
Frequently asked questions
What is the diameter of 12 gauge wire?
0.0808 in, or 2.05 mm, for solid wire. Its area is 3.31 mm² or 6,530 circular mils.
Is 2.5 mm² the same as 14 AWG?
Not quite. 2.5 mm² sits between 14 AWG (2.08 mm²) and 12 AWG (3.31 mm²), closest to 13 AWG. Building codes do not treat them as interchangeable.
More wire calculators
-
Wire Size Calculator
The right wire gauge for a circuit, by amps, distance and voltage drop.
-
Voltage Drop Calculator
Voltage lost along a copper or aluminum run, in volts and percent.
-
Wire Ampacity Chart
How many amps a wire carries, with heat and bundling derating.
-
Wire Resistance Calculator
Resistance of any length of wire, by metal, size and temperature.
-
Copper to Aluminum Wire Size
The aluminum size that replaces a copper wire, and how they compare.
-
Conduit Fill Calculator
How full a conduit is, and the smallest size that fits your wires.
-
Box Fill Calculator
Required box volume for the wires, devices and clamps in a box.