Wire Resistance Calculator

Work out the resistance of any length of wire from its metal, gauge or diameter and temperature, with the voltage drop and power loss at a given current.

Length in
mm²
mm
ft
°C

20°C is room temperature. Fully loaded building wire runs at 60 to 90°C.

A

Add it to see the voltage drop and the heat lost in the wire.

Resistance —
The same wire in other metals

How to use the wire resistance calculator

  1. Pick the material.
  2. Give the size as an AWG gauge, an area in mm² or a diameter in mm.
  3. Enter the length and the temperature of the wire. Tick count the length twice for a circuit, where current goes out on one wire and back on another.
  4. Optionally enter a current to see the voltage drop and the heat in the wire.

The formula

R = ρ × L ÷ A × (1 + α × (T − 20))

  • ρ (rho) is the resistivity of the metal at 20°C, in ohm-meters: 1.724 × 10⁻⁸ for annealed copper.
  • L is the length in meters and A the cross-section in square meters.
  • α (alpha) is the temperature coefficient: about 0.0039 per °C for copper and 0.0040 for aluminum.
  • T is the wire temperature in °C.

Example: 100 ft (30.48 m) of 12 AWG copper (3.31 mm²) at 20°C: R = 1.724 × 10⁻⁸ × 30.48 ÷ 3.31 × 10⁻⁶ = 0.159 Ω. At 75°C it rises by a factor of 1 + 0.00393 × 55 = 1.22, to 0.193 Ω.

Resistivity of common conductor metals

MetalResistivity at 20°C (Ω·m)Conductivity (% IACS)
Silver1.59 × 10⁻⁸108%
Copper, annealed1.724 × 10⁻⁸100%
Gold2.44 × 10⁻⁸71%
Copper-clad aluminumabout 2.65 × 10⁻⁸about 65%
Aluminum 13502.826 × 10⁻⁸61%
Brassabout 6.2 × 10⁻⁸about 28%
Low-carbon steelabout 1.4 × 10⁻⁷about 12%
Stainless steel 304about 7.2 × 10⁻⁷about 2.4%
Nichrome 80/20about 1.1 × 10⁻⁶about 1.6%

% IACS compares conductivity with the International Annealed Copper Standard. Alloys vary with their exact composition and temper, so their figures are typical values.

Why temperature matters

Metal resistance rises as it warms. A copper wire carrying its full rated current can run at 60 to 90°C, where its resistance is 16 to 28% higher than on the bench at 20°C. That is why the NEC resistance tables, and the voltage drop calculator, use 75°C. Nichrome is the opposite case: its resistance hardly changes with heat, which is why it is used in heating elements.

Frequently asked questions

Does stranded wire have more resistance than solid?

Slightly, about 2%, because each strand follows a spiral and is a little longer than the cable. The NEC tables list both.

Is CCA wire as good as copper?

No. Copper-clad aluminum has roughly 1.5 times the resistance of copper of the same size, so it drops more voltage and runs hotter. It is not allowed for PoE data cable under most standards. See copper vs aluminum wire.