Wire Resistance Calculator
Work out the resistance of any length of wire from its metal, gauge or diameter and temperature, with the voltage drop and power loss at a given current.
How to use the wire resistance calculator
- Pick the material.
- Give the size as an AWG gauge, an area in mm² or a diameter in mm.
- Enter the length and the temperature of the wire. Tick count the length twice for a circuit, where current goes out on one wire and back on another.
- Optionally enter a current to see the voltage drop and the heat in the wire.
The formula
R = ρ × L ÷ A × (1 + α × (T − 20))
- ρ (rho) is the resistivity of the metal at 20°C, in ohm-meters: 1.724 × 10⁻⁸ for annealed copper.
- L is the length in meters and A the cross-section in square meters.
- α (alpha) is the temperature coefficient: about 0.0039 per °C for copper and 0.0040 for aluminum.
- T is the wire temperature in °C.
Example: 100 ft (30.48 m) of 12 AWG copper (3.31 mm²) at 20°C: R = 1.724 × 10⁻⁸ × 30.48 ÷ 3.31 × 10⁻⁶ = 0.159 Ω. At 75°C it rises by a factor of 1 + 0.00393 × 55 = 1.22, to 0.193 Ω.
Resistivity of common conductor metals
| Metal | Resistivity at 20°C (Ω·m) | Conductivity (% IACS) |
|---|---|---|
| Silver | 1.59 × 10⁻⁸ | 108% |
| Copper, annealed | 1.724 × 10⁻⁸ | 100% |
| Gold | 2.44 × 10⁻⁸ | 71% |
| Copper-clad aluminum | about 2.65 × 10⁻⁸ | about 65% |
| Aluminum 1350 | 2.826 × 10⁻⁸ | 61% |
| Brass | about 6.2 × 10⁻⁸ | about 28% |
| Low-carbon steel | about 1.4 × 10⁻⁷ | about 12% |
| Stainless steel 304 | about 7.2 × 10⁻⁷ | about 2.4% |
| Nichrome 80/20 | about 1.1 × 10⁻⁶ | about 1.6% |
% IACS compares conductivity with the International Annealed Copper Standard. Alloys vary with their exact composition and temper, so their figures are typical values.
Why temperature matters
Metal resistance rises as it warms. A copper wire carrying its full rated current can run at 60 to 90°C, where its resistance is 16 to 28% higher than on the bench at 20°C. That is why the NEC resistance tables, and the voltage drop calculator, use 75°C. Nichrome is the opposite case: its resistance hardly changes with heat, which is why it is used in heating elements.
Frequently asked questions
Does stranded wire have more resistance than solid?
Slightly, about 2%, because each strand follows a spiral and is a little longer than the cable. The NEC tables list both.
Is CCA wire as good as copper?
No. Copper-clad aluminum has roughly 1.5 times the resistance of copper of the same size, so it drops more voltage and runs hotter. It is not allowed for PoE data cable under most standards. See copper vs aluminum wire.
More wire calculators
-
Wire Size Calculator
The right wire gauge for a circuit, by amps, distance and voltage drop.
-
Voltage Drop Calculator
Voltage lost along a copper or aluminum run, in volts and percent.
-
Wire Ampacity Chart
How many amps a wire carries, with heat and bundling derating.
-
AWG Wire Gauge Chart
Diameter, area in mm² and kcmil, and resistance for every gauge.
-
Copper to Aluminum Wire Size
The aluminum size that replaces a copper wire, and how they compare.
-
Conduit Fill Calculator
How full a conduit is, and the smallest size that fits your wires.
-
Box Fill Calculator
Required box volume for the wires, devices and clamps in a box.