Box Fill Calculator
Count the wires, devices, clamps and grounds in an electrical box and check the volume they need against the box, by NEC 314.16.
How to use the box fill calculator
- Pick the box. Metal boxes are listed with their NEC volume; for plastic boxes, enter the volume molded inside.
- Count the insulated wires of each size that enter the box or are spliced in it. A 12/2 cable brings two (the black and the white).
- Enter the number of devices and any fixture studs, and tick whether there are grounds and internal clamps.
The calculator adds up the required volume, says whether it fits and lists the standard boxes that are big enough.
How box fill is counted (NEC 314.16(B))
| Item | Counts as |
|---|---|
| Each insulated wire entering the box or spliced in it | 1 wire of its size |
| Wire passing through without a splice | 1 wire (2 if it loops 12 in or more) |
| Pigtails that start and end in the box | 0 |
| All equipment grounding wires together | 1 wire of the largest ground |
| All internal cable clamps together | 1 wire of the largest size |
| Each fixture stud or hickey | 1 wire of the largest size |
| Each device yoke (switch, receptacle) | 2 wires of the largest size connected to it |
Each “wire” then takes the volume in the table below.
Volume per wire (NEC Table 314.16(B))
| Wire size | Volume |
|---|---|
| 14 AWG | 2.00 cu in |
| 12 AWG | 2.25 cu in |
| 10 AWG | 2.50 cu in |
| 8 AWG | 3.00 cu in |
| 6 AWG | 5.00 cu in |
Example
A receptacle box with two 12/2 cables (one in, one out): 4 insulated 12 AWG wires = 9.00 cu in, one receptacle = 4.50 cu in, the grounds = 2.25 cu in. Total 15.75 cu in. A 3 × 2 × 2-1/2 in metal device box holds only 12.5 cu in, so it is too small; an 18 cu in plastic box or a 4 in square box with a mud ring works.
Tips
- A box that only just passes is hard to work in. Leave some spare room, especially with GFCI and smart switches, which are much deeper than plain devices.
- Extension rings and raised covers add their marked volume.
- Conduit bodies and boxes over 100 cu in, or with 4 AWG and larger wire, follow different rules (NEC 314.16(C) and 314.28).
Choosing wire for the circuit first? Start with the wire size calculator.
Frequently asked questions
Do ground wires count in box fill?
Yes, but all of them together count as one wire of the largest ground size. A second, separate set of isolated grounds (for sensitive equipment) adds one more allowance.
How many wires can go in a single-gang box?
It depends on the box volume and the devices. An 18 cu in box with one device and grounds has room for five 12 AWG wires (18 ÷ 2.25 = 8 allowances, minus 2 for the device and 1 for the grounds).
More wire calculators
-
Wire Size Calculator
The right wire gauge for a circuit, by amps, distance and voltage drop.
-
Voltage Drop Calculator
Voltage lost along a copper or aluminum run, in volts and percent.
-
Wire Ampacity Chart
How many amps a wire carries, with heat and bundling derating.
-
AWG Wire Gauge Chart
Diameter, area in mm² and kcmil, and resistance for every gauge.
-
Wire Resistance Calculator
Resistance of any length of wire, by metal, size and temperature.
-
Copper to Aluminum Wire Size
The aluminum size that replaces a copper wire, and how they compare.
-
Conduit Fill Calculator
How full a conduit is, and the smallest size that fits your wires.