Conduit Fill Calculator

Check how full a conduit is with THHN/THWN wires, and find the smallest EMT, PVC or rigid conduit that meets the NEC fill limits.

THHN / THWN-2 wires in the conduit, including the ground
Conduit fill —
Fill in every trade size

How to use the conduit fill calculator

  1. Pick the conduit type and trade size.
  2. Enter up to four groups of wires, each with its size and number. Include the equipment ground: it counts toward the fill.
  3. Tick nipple for a short conduit 24 in long or less between boxes or enclosures.

The calculator adds up the wire areas, compares them with the allowed area of the conduit and shows the fill for every trade size of that type, with the smallest one that works.

The fill limits (NEC Chapter 9, Table 1)

Number of wiresMaximum fill
153%
231%
3 or more40%
Nipple, 24 in or shorter60%

Two wires get the lowest limit because two round wires can jam side by side in a bend. The limits leave room to pull the wires in without damaging the insulation, and to let heat escape.

The formula

Fill % = total wire area ÷ conduit area × 100

Wire areas come from NEC Chapter 9 Table 5 and conduit areas from Table 4. Example: three 12 AWG THHN and one 12 AWG ground (4 × 0.0133 = 0.0532 sq in) in 1/2 in EMT (0.304 sq in) fill 17.5%, well under 40%.

Maximum THHN wires of one size

Wire1/2 in EMT3/4 in EMT1 in EMT
14 AWG122235
12 AWG91626
10 AWG51016
8 AWG369
6 AWG146

When every wire is the same size, NEC Chapter 9 Note 7 lets you round up a result with a decimal of 0.8 or more. The calculator applies it.

Fill is not the only limit

  • Ampacity: more than three current-carrying wires in one conduit reduces what each can carry. Check with the ampacity calculator.
  • Bends: no more than 360° of bends between pull points.
  • Jamming: three wires whose diameters add up to nearly the conduit’s inside diameter can wedge in a bend. Going up one size makes the pull much easier.
  • Other wire types (XHHW, RHW, cable) have different areas. This calculator covers THHN, THWN and THWN-2.

Frequently asked questions

How many 12 gauge wires can go in 1/2 EMT?

Nine 12 AWG THHN, ground included. In practice, fewer wires make the pull easier and need less ampacity derating.

Does the ground wire count in conduit fill?

Yes. Every wire in the conduit counts toward the fill. The ground does not count when derating for the number of current-carrying conductors.

More wire calculators