Copper to Aluminum Wire Size
Find the aluminum wire that replaces a copper one, or the other way round, matched by ampacity, with the resistance and weight of each.
How to use the copper to aluminum wire size calculator
- Choose copper to aluminum or aluminum to copper.
- Pick the wire size you have, or the size a plan or chart calls for.
- Pick the temperature rating. Feeders, services and most panels use 75°C.
The result is the smallest wire of the other metal whose NEC Table 310.16 ampacity is at least as high, with the resistance and bare-metal weight per 1,000 ft of both.
The rule of thumb: two sizes up
Aluminum conducts about 61% as well as copper, so an aluminum wire needs about 1.6 times the area to carry the same current. In AWG steps that is usually two sizes larger:
| Copper (75°C) | Aluminum equivalent | Typical use |
|---|---|---|
| 10 AWG (30 A) | 8 AWG | Water heater, dryer |
| 8 AWG (50 A) | 6 AWG | Range, EV charger |
| 6 AWG (65 A) | 4 AWG | 60 A subpanel |
| 4 AWG (85 A) | 2 AWG | Subpanel, heat pump |
| 2 AWG (115 A) | 1/0 AWG | 100 A feeder |
| 1/0 AWG (150 A) | 3/0 AWG | 150 A feeder |
| 2/0 AWG (175 A) | 4/0 AWG | Service conductors |
| 3/0 AWG (200 A) | 250 kcmil | 200 A feeder |
Dwelling services and main feeders may use the smaller sizes allowed by NEC 310.12, which is why a 200 A home service often uses 4/0 aluminum rather than 250 kcmil.
What else changes
- Weight: the equivalent aluminum wire weighs about half as much as the copper, which matters on long feeders and overhead spans.
- Resistance: the equivalent sizes have close to the same resistance, so the voltage drop is about the same. Check long runs with the voltage drop calculator.
- Diameter: the bigger wire needs a bigger conduit and lugs that accept it. Check with the conduit fill calculator.
- Terminations: aluminum must go only on terminals marked AL/CU (or CO/ALR for 15 and 20 A devices), torqued to the stated value, with anti-oxidant compound where the maker calls for it.
Read the full comparison in copper vs aluminum wire.
Frequently asked questions
What size aluminum wire for 100 amps?
1 AWG aluminum at 75°C (100 A) for a feeder. For a 100 A dwelling service or main feeder, NEC 310.12 allows 2 AWG aluminum.
Can I use aluminum for 15 and 20 amp branch circuits?
It is allowed with the right devices, but almost never done today. Small solid aluminum branch wiring from the 1960s and 70s caused connection failures; modern AA-8000 alloy is used mainly in sizes 8 AWG and larger.
More wire calculators
-
Wire Size Calculator
The right wire gauge for a circuit, by amps, distance and voltage drop.
-
Voltage Drop Calculator
Voltage lost along a copper or aluminum run, in volts and percent.
-
Wire Ampacity Chart
How many amps a wire carries, with heat and bundling derating.
-
AWG Wire Gauge Chart
Diameter, area in mm² and kcmil, and resistance for every gauge.
-
Wire Resistance Calculator
Resistance of any length of wire, by metal, size and temperature.
-
Conduit Fill Calculator
How full a conduit is, and the smallest size that fits your wires.
-
Box Fill Calculator
Required box volume for the wires, devices and clamps in a box.