Wiring a circuit? THHN and NM-B wire on Amazon (opens in a new tab)

Voltage Drop Calculator

Work out the voltage lost along a copper or aluminum wire, in volts and percent, for single-phase, three-phase and DC circuits.

Length in
V
A
ft
Voltage drop —
Voltage drop by wire size

How to use the voltage drop calculator

  1. Pick copper or aluminum and the wire size.
  2. Pick the circuit: single-phase AC and DC circuits have two current-carrying wires; three-phase circuits have three.
  3. Enter the source voltage, the current the load draws and the one-way length of the run.

You get the drop in volts and percent, the voltage left at the load, the heat lost in the wire, the longest run that stays within 3%, and the same figures for every other size.

The formula

Vd = 2 × I × R × L ÷ 1,000 (single-phase and DC)

Vd = 1.732 × I × R × L ÷ 1,000 (three-phase)

  • I is the load current in amps.
  • R is the conductor resistance in ohms per 1,000 ft. The calculator uses NEC Chapter 9 Table 8, which gives the DC resistance of stranded wire at 75°C, a typical temperature for a loaded wire.
  • L is the one-way length in feet.

Percent drop = Vd ÷ source voltage × 100.

Example: a 20 A load at 120 V, 100 ft from the panel, on 12 AWG copper (1.98 Ω per 1,000 ft). Vd = 2 × 20 × 1.98 × 100 ÷ 1,000 = 7.9 V, or 6.6%. Only 112 V reaches the load. 10 AWG brings it down to 4.1%, and 8 AWG to 2.6%.

How much voltage drop is acceptable?

CircuitUsual limit
Branch circuit (panel to outlet)3%
Feeder plus branch circuit, total5%
Sensitive electronics, long motor runs2%
12 V low-voltage lighting and solar3% to 10%, check the product

The 3% and 5% figures come from informational notes in the NEC (210.19 and 215.2), so they are recommendations, not hard rules, in most places. Some energy codes, and the rules for fire pumps and some other equipment, do make limits mandatory.

Why voltage drop matters

  • Lights dim and heaters lose output: a 6% drop cuts a heater’s power by about 12%.
  • Motors run hot and draw more current, which shortens their life and can trip overloads.
  • Energy is wasted as heat in the wire, every hour the load runs.
  • Low-voltage systems are hit hardest: losing 1 V is under 1% at 120 V but 8% at 12 V.

How to reduce voltage drop

  1. Use a larger wire. Each step up of three AWG sizes halves the resistance.
  2. Use a higher voltage. The same power at 240 V draws half the current of 120 V, and the percent drop falls to a quarter.
  3. Shorten the run, or put a subpanel closer to the loads.
  4. Switch to copper, or go up two sizes if you stay with aluminum. See the copper to aluminum wire size calculator.

Read the step-by-step guide how to calculate voltage drop, or let the wire size calculator pick a size that passes both the ampacity and voltage drop tests.

Frequently asked questions

Is the length one way or round trip?

Enter the one-way length. The formula’s 2 (or 1.732 for three-phase) already accounts for the return path.

Does power factor change the result?

For wire up to about 1/0 AWG the DC resistance method is accurate enough. For large conductors in steel conduit with a low power factor, the AC impedance in NEC Chapter 9 Table 9 gives a slightly higher drop.

More wire calculators